Key takeaways
- A walk-in usually needs separate circuits for the condensing unit and the evaporator, sized from each nameplate, plus the door heaters and lights.
- Each refrigeration unit needs a disconnect within sight, and rooftop equipment needs a service outlet nearby.
- Plan for the outage: an alarm, a known circuit, and a standby generator or transfer plan for the coldest stock.
Walk-in cooler electrical requirements are set by the refrigeration equipment that comes with the box. The panels and door are the easy part. The condensing unit, the evaporator coil, the door heaters and the lights each have their own electrical needs, and a restaurant or commercial kitchen cannot afford a walk-in that trips at two in the morning.
What circuits does a walk-in cooler need?
- A circuit for the condensing unit, often 208 or 240 volts, sometimes three phase, sized from its nameplate.
- A circuit for the evaporator inside the box, sized from its own nameplate; on a freezer this includes the defrost heaters.
- Power for the door frame heaters on a freezer, so the door does not freeze shut, and for the interior light.
- In some packaged systems, one circuit feeds everything through the unit's own controls.
The nameplates list the minimum circuit ampacity and the maximum overcurrent protection, and those numbers set the wire and breaker sizes. The National Electrical Code has a separate article for refrigeration and air conditioning equipment built around them.
Where do the disconnects go?
Each refrigeration unit needs a disconnecting means within sight of it, so the technician working on it can shut it off and see that it stays off. For a condensing unit on the roof, that is a weatherproof disconnect beside it on the roof. For the evaporator, it is usually near the coil inside or on the box wall.
Rooftop units also need a service receptacle within reach of the equipment, so the refrigeration technician has power to work without running a cord up a ladder. It is a frequent inspection item on restaurant jobs.
Does the condensing unit go inside or on the roof?
Either, and the electrical follows the choice. A rooftop unit means a longer run, a roof penetration and the disconnect and service outlet up there. A unit set indoors or in a mechanical area is a shorter run but puts heat into the building. The refrigeration contractor usually makes the call with the landlord; we wire to it.
How do I keep a walk-in running in an outage?
Start with knowing exactly which breakers feed it, labeled in the panel. Add a temperature alarm that texts someone. For a restaurant where one night's loss would hurt, a standby generator or a transfer switch ready for a portable unit is worth the conversation. Our post on a restaurant standby generator covers sizing for the refrigeration load.
Who installs what?
The refrigeration contractor sets the box, the condensing unit and the evaporator, runs the refrigerant lines and charges the system. The electrician runs the circuits, sets the disconnects and the service outlet, and makes the power connections. On a build-out, both are coordinated by the general contractor so the power is ready when the box goes up.
Does walk-in cooler wiring need a permit in San Antonio?
Yes. New commercial circuits are permitted work, pulled by the licensed electrical contractor, and inspected. Our guide to how commercial electrical permits work in San Antonio walks through the steps, and the City's code amendments are in Chapter 10 of its city code.
If the kitchen is going into a vacant space, our post on a vacant suite electrical make-ready covers what to check before the tenant work starts. Send the equipment schedule to our commercial electrical team and we will write the price before the work starts.