Key takeaways
- Most workplace and customer sites use Level 2 chargers; DC fast chargers draw far more power.
- A load study shows whether the existing service can carry chargers before any are bought.
- AEP Texas bills secondary service over 10 kW on the highest 15 minute demand of the month.
- NEC Article 625 covers charging equipment, and the City permit and inspections run through the Dynamic Portal.
- AEP Texas asks to be told before service entrance equipment is changed.
EV charging for a Corpus Christi business usually means chargers for employees at work or for customers who park while they shop, eat or stay. Both run on the same electrical questions: how much spare capacity the service has, what the chargers will do to the demand on the bill, which NEC rules apply, what the City permit covers and when AEP Texas has to be told. This guide covers workplace and customer charging. Company vehicles that return to a yard overnight follow a different load pattern, covered in our guide to fleet EV charging in Corpus Christi.
Which chargers suit workplace and customer parking?
Most workplace and customer sites use Level 2 chargers, which run on 208 or 240 volt circuits and suit cars parked for a few hours. DC fast chargers suit short stops, such as a quick break on a road trip, and draw far more power, which often means new service capacity and more utility coordination.
The choice follows how long cars stay. Employees parked for a shift can fill up slowly, so a row of Level 2 chargers sharing a feeder is the common answer. A hotel or restaurant may want a mix: Level 2 for guests who stay, and perhaps one fast charger for drivers passing through. Networked chargers add payment, access control and reporting, while simpler units just deliver power. Each choice changes the circuit sizes, the panel space and the conduit runs, so it is settled before the electrical design starts, not after the chargers arrive on site.
How do you know whether the building has capacity for chargers?
With a load study. An electrician compares what the service is rated to carry against what the building actually draws, using a year of utility demand data or a recorded measurement, and the NEC Article 220 calculation. The space left over, with a sensible margin, is what chargers can use without new service.
The study looks at the main service, the panel the chargers would feed from, and the path between them. Panel space matters as much as amperes: a panel with capacity but no open spaces still needs work. If the margin is thin, there are choices short of a bigger service, such as load management that shares one feeder among several chargers and holds the total under a set limit. The study also shows the busiest hours of the building's day, which shapes the charging schedule that comes next and what it will do to the bill.
How do chargers affect the AEP Texas demand charge?
AEP Texas bills non-residential secondary service over 10 kW per kW of billing demand, measured as the highest 15 minute period of use in the month. Chargers that all start at once in the busiest part of the day can set a new peak, and that peak drives the delivery charge for the month.
Larger premises add a second measure. Under the tariff, a premises that has reached 700 kW in any previous billing month is billed transmission on 4CP, its average demand at the four ERCOT monthly peaks from June to September of the prior year. Charging held off those summer afternoon peaks matters for such a site. Managed charging, which staggers or slows chargers when the building load is high, is the usual tool. On AEP Texas service, your retail electric provider bills you, and AEP Texas bills its delivery charges to that provider, so the structure shows up inside your monthly bill.
Sources: AEP Texas's Tariff for Retail Delivery Service, Sections 5.8.1 and 6.1.1.1.3, and AEP's Guide for Electric Service and Meter Installations (2026), Section 4.1.
What does NEC Article 625 require?
Article 625 is the part of the National Electrical Code written for electric vehicle charging equipment. It requires listed equipment, treats charging as a continuous load so circuits are sized above the charger's rating, and sets rules for disconnecting means, ground fault protection for people, and where equipment may be mounted outdoors.
Article 625 works with the rest of the code. The feeder and branch circuits follow Articles 210 and 215, the load study follows Article 220, and any change at the service follows Article 230. When load management is used to share capacity, the code allows the managed limit to set the load, provided the system controlling it meets its own requirements. The edition matters as well: the City's posted code page lists the 2020 NEC with local amendments, and Texas adopted the 2026 NEC statewide from September 1, 2026, so the design follows the edition the permit office reviews under.
When does AEP Texas need to know about the project?
Whenever the job changes the service. AEP's guide says the customer must notify the company before altering service entrance equipment so it can provide facilities of proper capacity. Chargers that fit on the existing service need no AEP work, but a larger service, a new transformer or a new meter starts with AEP Texas.
AEP Texas's tariff lists six items every construction request must include: the contact name, the contact phone, the ESI ID if one exists, the service address with directions, the service requested and the requested date. It says AEP Texas will contact the requester within two business days, and that it does not guarantee construction timelines, so the request goes in early. AEP Texas serves the majority of Corpus Christi, while Nueces Electric Cooperative serves parts of Nueces County, so the first step is confirming which one serves the site.
Sources: AEP's Guide for Electric Service and Meter Installations (2026), Section 4.5, the AEP Texas new business service form, the tariff's Section 5.3 and the City's page naming the area's electric providers.
What permit does a charger installation need in Corpus Christi?
A City electrical permit, which we apply for in the City's Dynamic Portal before work starts. Electrical permits are available online there, and the portal handles fees, review comments and inspections. When chargers are part of a larger building project, the electrical permit is a child permit issued after the master building permit.
Inspections show in the portal only once fees are paid. The City's local amendments say the inspector is to inspect within 2 days of notice, and the trade permit application says final inspections close the permit. Where the job adds new service, AEP Texas connects only after it is told the proper authority approved the installation. Wattsmith Electric registers with the City of Corpus Christi before a permit is bought, as the City requires.
Sources: the City's building permits page, its Dynamic Portal guides, the commercial permit checklist (DSD-2001) and the trade permit application (DSD-1026).
Where should chargers go on a coastal site?
As close to the electrical room or panel as parking allows, since shorter runs mean less trenching and less voltage drop. Chargers also need protection from vehicles, clear access for drivers, and on this coast, attention to salt air, with enclosures, hardware and fittings chosen for outdoor exposure as general practice.
Underground runs to parking are common, and the City's local amendments say only nonmetallic conduit may generally be installed underground. Pedestals and wall units in open lots face sun, rain and salty wind, so the charger's own outdoor rating and its mounting hardware deserve a look before purchase. AEP's guide sets a corrosion rule for CT enclosures within 30 miles of the coast, which applies to the metering where a CT service is involved, not to the chargers themselves. The price of the job is worked out from the load study and the layout, and it is set after the free written estimate.
We install workplace and customer chargers through our Corpus Christi EV charging service. For company vehicles, see fleet EV charging in Corpus Christi; for outdoor gear, see coastal electrical work and salt air in Corpus Christi. The rest of our work in the city is on the Corpus Christi commercial electrician hub and under commercial electrical services.